GENERAL
UPS Topology
Online Double Conversion |
Energy Saving Technology
Online ECO Mode Efficiency > 96% |
Active PFC Compatibility
Yes |
Parallel Expansion (Max. Units)
4 |
INPUT
Generator Compatibility
Yes |
Nominal Input Voltage (Vac)
230 |
Input Voltage Range (Vac)
110 ~ 276 |
Adjustable Voltage Range (Vac)
0~80% Load for 110 ~ 276 Vac |
0~100% Load for 176 ~ 276 Vac |
Input Frequency (Hz)
50 ± 5 |
60 ± 6 |
Input Frequency Detection
Auto-sensing |
Rated Input Current (A)
45.5 |
Input Power Factor
0.99 |
Input Connector Type
Hardwire Terminal Block |
OUTPUT
Capacity (VA)
10000 |
Capacity (Watts)
9000 |
On Battery Waveform
Pure Sine Wave |
On Battery Voltage(s) (Vac)
208 ± 1% |
220 ± 1% |
230 ± 1% |
240 ± 1% |
Output Voltage Setting
Configurable |
On Battery Frequency (Hz)
50 ± 0.1% |
60 ± 0.1% |
Output Frequency Setting
Configurable |
Power Factor
0.9 |
ECO Mode Voltage Tolerance
± 10 % |
Overload Protection
Internal Current Limiting , Circuit Breaker , Fuse |
Overload Protection (Line Mode)
105~125% Load for 10 min, 125~150% Load for 1 min, 150~170% Load for 10 sec, >170% Load for 1 sec |
Overload Protection (Battery Mode)
105~125% Load for 2 min, 125~150% Load for 30 sec, >150% Load for 1 sec |
Overload Protection (Bypass Mode)
125~150% Load for 1 min, 150~170% Load for 10 sec, >170% Load for 1 sec |
Crest Factor
3 : 1 |
Harmonic Distortion (Linear Load)
THD<2% |
Harmonic Distortion (Non-linear Load)
THD<5% |
Internal Bypass
Automatic Bypass |
Outlet(s) – Total
1 |
Outlet Type
Hardwire Terminal Block x 1 |
Typical Transfer Time (ms)
0 |
BATTERY
Maximum Charging Current (A)
4 |
Start On Battery
Yes |
Smart Battery Management (SBM)
Yes |
User-replaceable
No |
Extended Battery Module (EBM)
BPSE240V75ART3U |
Max. EBM Quantity (pcs)
15 |
SURGE PROTECTION & FILTERING
Surge Suppression (Joules)
445 |
EMI/RFI Filtration
Yes |
MANAGEMENT & COMMUNICATIONS
LCD Panel
Yes |
LCD Information Display
Operation Type , Power Status , Battery Status , Load Status , Fault & Warning , Other Information , Event & Log |
LCD Setting & Control
Mode Setting , Alarm Setting , Input & Output , Battery Setting , Fault & Warning , Communication , Event & Log , Security Setting |
LED Indicators
Line Mode , Battery Mode , Bypass Mode , UPS Fault |
HID Compliant USB Port(s)
1 |
Serial Port
RS232 |
Dry Contact (with Relay)
Optional |
Emergency Power Off (EPO) Port
Yes |
Audible Alarms
Battery Mode , Low Battery , Overload , Overcharge , Overheat , UPS Fault |
Power Management Software
PowerPanel® Business Edition |
SNMP/HTTP Remote Monitoring
Yes – with optional RMCARD205 |
PHYSICAL
Form Factor
Rack/Tower |
Enclosure Construction
Metal |
Color
Black |
Rackmount Rail
Yes |
PHYSICAL SIZE – POWER MODULE
Dimensions (WxHxD) (in.)
17.24 x 5.14 x 26.77 |
Dimensions (WxHxD) (mm.)
438 x 130.5 x 680 |
Weight (lbs.)
44.1 |
Weight (kg.)
20 |
Installed Rack Height (U)
3 |
PHYSICAL SIZE – BATTERY MODULE
Dimensions (WxHxD) (in.)
17.24 x 5.14 x 26.77 |
Dimensions (WxHxD) (mm.)
438 x 130.5 x 680 |
Weight (lbs.)
121.3 |
Weight (kg.)
55 |
Installed Rack Height (U)
3 |
มาเป็นคนแรกที่วิจารณ์ “CyberPower CBP-OLS10000ERTXL3U UPS OLS Series RT 10000VA/9000W By Vnix Group”